Accurate Powertech India Pvt. Ltd.

Air Cooled Gensets, Water Cooled Gensets, Air Cooled DG Sets, Water Cooled Diesel Generators, Air Cooled Diesel Gensets, Water Cooled Diesel Generator Sets, Diesel Engines, Kirloskar (KOEL), Gensets (Generators / Diesel Engines / DG Sets) Dealer, Supplier, Pune, Maharashtra, India

Gensets - Air Cooled -

Zee Business Dare to Dream Award

We are the leading trader and wholesaler of Air Cooled Generator Set which are made by using superior quality of raw materials. It has lower life cycle cost and is eco friendly. Our Air Cooled Generator Set supply power during temporary outages. They are suited to both residential and commercial environments. They are used in industry, construction, mining, agriculture, telecommunications, retail, education, IT, hospitality, and tourism, healthcare and for marine applications. These are provided at industry leading rates.

Features :

  • Air cooled
  • Easy usage
  • Low on maintenance

Prime Rating at rated rpm ( as per ISO8528 )1 kVA 5 7.5 10 15 25 40 62.5
kW 4 6 8 12 20 32 50
Genset Model KG1-5AS1> KG1-7.5AS KG1-10AS1 KG1-15AS KG1-25AS KG1-40AS KG1-62.5AS
Frequency Hz 50 50 50 50 50 50 50
Power factor lagging 0.8 0.8 0.8 0.8 0.8 0.8 0.8
Voltage V 230 (1Ø ) 230 (1Ø ) & 415 (3Ø) 415 (3Ø)
Governing class ( As per ISO 8528 Part-V ) G2 G2 G2 G2 G2 G2 G2
Noise level dBA < 75 < 75 < 75 < 75 < 75 < 75 < 75
Fuel Consumption* At 100 % Load Ltrs/hr 1.6 2.3 3.0 4.0 6.4 9.9 16.2
At 75 % Load 1.3 1.8 2.4 3.0 5.0 7.9 12.7
At 50 % Load 1.0 1.4 1.8 2.2 4.0 5.8 8.9
Fuel Tank Capacity Ltrs 70 30 30 65 65 100 150
Overall dimensions of genset (L x W x H)^ mm 1600 x
820 x
1530
1760 x
820 x
1330
1760 x
820 x
1330
1772 x
1050 x
1410
2130 x
1050 x
1520
2420 x
1050 x
1670
3176 x
1200 x
1632
Dry weight of genset with canopy (approx..)^ Kg 650 750 750 950 1050 1400 1750
Wet weight of genset with canopy (approx..)^ Kg 700 800 800 1000 1100 1500 1875
Electrical Battery starting voltage Volts-DC 12 12 12 12 12 12 12
ENGINE
Engine Model EA10G1 EA16G1 EA16 G1 HA294 G1 HA394 TCI G1 HA494TCI G1 HA694TCI G1
Rated output (Prime Continuous rating as per ISO 8528-1) kW 7.3 11.8 11.8 15.1 23.5 41.19 61.0
HP 10 16 16 20.5 32 56 83
No. of cylinder Number 1 2 2 2 3 4 6
Cubic capacity 2 Ltrs 0.95 1.56 1.56 1.88 2.89 3.77 5.65
Bore x Stroke mm 102 x 116 95 x 110 95 x 110 100 x 120 100 x 120 100 x 120 100 x 120

Rated Speed

RPM 1500 1500 1500 1500 1500 1500 1500
Aspiration NA/TC/TA NA NA NA NA TC TC TC
Lube Oil change period hrs. 500 500 500 500 500 500 500
Lube oil Sump Capacity Max Ltrs 3.5 6.5 6.5 5.0 8.0 8.3 11.0
ALTERNATOR
Insulation Class Class H
Alternator Effciency (at 100% load) 0.8 pf** % 74.6 78.1 78.6 83.5 88.8 89.2 91.0
Max Voltage Dip at Full Load 0.8 pf Lag < 20% < 20% < 20% < 20% < 16% < 16% < 20%
Max Time to build up rated voltage at Rated RPM sec < 5 sec provided engine reach the rated speed